Chapter 1 Device features and technical parameters
Section 1 Main features(LY808 Relay Protection Analyzer)
¿Flexible combination of voltage and current output
Six phase voltage and six phase current can be output,
which has made it is possiable to be any combition, such as the output mode of the
combination of conventional four phase current and three-phase current, six phase
voltage mode, six phase current mode and 12 phase output mode. It not only can
be compatible with the traditional way of various tests, but also can
conveniently carry out differential test of three-phase transformer.
¿Operation mode
The device is directly connected with a computer or a
desktop computer, which is convenient and efficient and stable performance.
¿A new hi-fi linear power amplifier
The output port has always insisted on using the modular
linear power amplifier instead of the switching power amplifier, which has the
high fidelity and high reliability function and excellent performance. High-mid
frequency will not be produced to disturb the test, also ensure the smoothing
accuracy of waveform produced by the whole course of the high current to the
tiny current is excellent.
¿High performance Mainframe
The output part adopts DSP control, which has fast
operation, real-time digital signal processing capability, wide bandwidth and high
resolution D/A conversion control. The output waveform has the features of high
precision, small distortion and good linearity. With using a large number of
advanced technology and precision components and materials and the structure of
professional design, the device has the features of small volume, light weight,
full function, easy to carry, boot can work, flow test is very convenient.
¿Powerful software function
It can complete all kinds of high automatic validation work
which is large and complex. It can also conveniently test and scan protection setting,
playback of fault, real-time store test data, display vector, online print report
and so on. Besides, six-phase current can facilitate the test of three-phase differential
protection.
¿IndependentDCpower output
An 110V and 220V adjustable DC power is designed to supply
output.
¿Complete interface
The device with USB communication port can communicate with
the computer and other external devices.
¿Perfect self-protection function
With reasonable design of the heat dissipation structure and
the reliable and perfect hardware protection measures, it has the power soft
start function and the software of the fault self-diagnosis and the output
latch function.
Section 2 Nominal parameter(LY808 Relay Protection Analyzer)
¿ Parameter
|
Type
|
|
|
Current channel number
|
Standard six phase
|
|
Voltage channel number
|
Standard six phase
|
|
AC current output range
|
30A / phase or 180A (six phase parallel)
|
|
DC current output range
|
10A DC /phase
|
|
AC voltage output range
|
120V AC /phase
|
|
DC voltage output range
|
160V DC / phase
|
¿ Nominal parameter
AC current output
The virtual value of each phase output when six phase
current output 0~30A output precision 0.1 grade
The virtual value of each phase output when three phase
current output 0~60A
The virtual value of six phase parallel current output 0~180A
The allowed virtual value when the phase current work long time
10A
The maximum output power of phase current 450VA
The maximum output power when six phase parallel current
output 1000VA
The allowed working time when six phase parallel current maximum
output 10s
Frequency range(fundamental wave) 0~1000Hz
Harmonic order
0~20
DC current output
Current output 0~±10A / phase output
precision 0.2 grade
The maximum load volatage output 20V
AC voltage output
The virtual value of phase voltage output 0~120V output precision 0.1 grade
The virtual value of line voltage output 0~240V
The output power of phase voltage/ line voltage 80VA / 100VA
Frequency range(fundamental wave) 0~1000Hz
Harmonic order
0~20
DC voltage output
The output amplitude of phase voltage 0~±160V output precision 0.2 grade
The output amplitude of line voltage 0~±320V
The output power of phase voltage/ line voltage 70VA / 140VA
Input and output
8 channels input
Free contact 1~20mA,24V
Electric potential contacts
“0”:0 ~ +6V; “1”:+11 V ~ +250 V
4 channels output DC:220 V/0.2 A;AC:220 V/0.5 A
Time measurment range
0.1ms ~ 9999s , measurement accuracy <0.1ms
Chapter 2 Hardware Structure(LY808 Relay Protection Analyzer)
Section 1
Hardware Structure
¿ Digital Signal Processor Microcomputer
High-speed digital controlling processor is adopted as the output
core of the tester. 32 bit double precision arithmetic is employed in the
software, through which arbitrary high-accuracy waveforms of each phase can be
produced. Since integrative structure is adopted, the structure of the tester
is layed compactly.The distance of data transmission is short with tight
structure, which overcome the problem of fewer points of waveform output due to
long data communicational line and narrow frequency band when using the test
controller controlled directly by PC.
¿ D/A Conversion and Low-Pass Filtering
High precision D/A converter is employed for ensuring the precision
and linearity of current and voltage in the whole range.
Due to high density of fitting ponit, fidelity of waveform
is high and harmonic component is small, which don’t have a strict requirement
on the low-pass filter. Consequently, it has good characteristics of transient,
phase frequency and amplitude frequency, which is easy to perform accurate
phase-shifting and harmonic superposition and ensures very high precision even
when the frequency is high.
¿ Voltage and Current Amplifier
For phase current and voltage, we persist in adopting high
performance linear amplifier output mode in order to make the current and
voltage source to directly output all kinds of waveforms from the DC waveform
to the waveforms including all kinds of frequency components, such as square
wave, combined waveform overlapped by each order harmonic, fault transient
waveform, etc. In addition, the output waveform is clear and smooth without
high-frequency radiated interference with neighboring equipments. It can
simulate well all kinds of current and voltage characteristics under the circumstance
of short circuit fault.
For power amplifier circuit, we adopt import power parts
with high-power and hi-fi module style as power output, combining with heat
dissipation structure layed elaborately and reasonably, it has enough large
power redundancy and thermal capacity. The power amplifier circuit has
overheat, overflow, overvoltage and short circuit protections. When overflow occurs
in the current circuit and overload or short circuit occurs in the voltage
circuit, it will limit the output power automatically, switch off the whole
power amplifier circuit and give alarm signal.In order to prevent the overheat of
the power amplifier for long time operating under large current, a software
time terminating system under large current is set in this tester. It can work
for a long period when outputting is 10A or below. When the current is over
10A, the tester will start up the software time termination order. When time is
up, the software will forbid power output automatically and give alarm signal.
The higher output current is, the shorter the limiting time will be.
¿ Input and output
This tester has 8 channels input and 4 channels output.
The switching input circuit is compatible for both the
empty contacts and 0-250V electric potential contacts in the input and output
circuit. When the electric potential contacts are selected, 0-6V belongs to
closed switch and 11-250V belongs to open switch. The switching capacity can
test the action time and the action time interval of every phase switch’s
contact conveniently.
The part of the digital input is isolated from the
resources of the mainframe and the amplifier. The end of the digital input is
hung, so the common end of the digital input is separated from the Common End UN,
IN of current and voltage parts.
Switching potential input has directivity, you should
connect the common end with the positive terminal of potential, and connecting
the input end with negative terminal of potential for ensuring the potential of
common end is higher than the one of input end. In practice, you should connect
the input common end with +KM, and connecting the
negative terminal of contact with input end.
The output part is the idle contact output of relay. Output
capacity is DC:220V/0.2A,AC:220V/0.5A. Output
of switching capacity is independent of voltage, current, input and all other
parts. Action process of each digital output part is different in each testing
module. For details, please refer to the operation instruction on software
module.
The connection diagram of two kinds of familiar digital
output is as follows:
Mode of potential contact
Mode of free contact
¿ Auxiliary DC Power Supply Output for Special Use
A circuit of special adjustable DC power supply output is
allocated on the rear panel, which has 110V and 220V two shifts that can be
used as test standby power supply on the spot. We still set a potentiometer for
this power supply, it can be adjusted within the range of 80%-110%. Rated current of this power supply is
1.5A, which can be used as DC power supply of protective tester or switch loop
supply. If overload or short circuit occurs, corresponding protector tube will
be burned out (2A/250V), you will only need to change this protector tube at that time.
Chapter 3 Please Read the Following
Instruction before Operation(LY808 Relay Protection Analyzer)
Section 1
General Rules for Use
Please do not shut off power supply directly during
outputting so as to avoid the wrong protection action due to incorrect output.
When switch quantity is compatible with both idle contact
and the potential (0~DC250V) and uses charged contact, the high terminal (anode) of contact
potential should be connected with the common end +KM.
When taking the tester into operation, make sure that the
air slots, the power switch and the power supply plug at the test set remain
unobstructed.The instrument should be laid uprightly, or unfold the bracket for
slightly tilted placement
Do not lead external AC/DC power into the voltage and
current output sockets of tester.
If the disturbance is stronger on the spot or high safety
is required, before doing the test, please ground the outlet of power source or
the protective earth of the tester.
If the interface data is wrong or you can not input
correctly when using this tester, you can settle the problem as follows: delete
the ‘para’ file under the ‘E\Relaytestar\, and then restart the running
program, all data on the interface will be resumed to the default.
Section 2
Procedures of turning on/off Tester
¿ Procedures for Turning On
Plug the power line of tester in AC220V outlet. If using
external computer, please connect well the serial communication line with
computer’s serial interface and the communication interface on the bottom of
the tester.
Method one: Start up the Windows operating system firstly,
and then enter the main software interface of ‘Relaytestar’.
Method two: It wills automatic recover the Windows
operating system, which will need four minutes. Then enter the interface which
can choose the way of starting up.This way is mainly used when the Windows
operating system is damaged and cannot nomal start, which can make the Windows
operating system restore to factory settings. The user cannot worry that the
previous test report and data will be losing after self-recovery. But this way
will take much time and it is not the best choice to often use.
Method three: This way will enter DOS state and mainly used
by the management personnel. If the user enters DOS state carelessly, please
turn off the power and wait a moment to boot again.
You can use the up and downs key or ‘1’,’2’,’3’ number key
to choose the boot way within five seconds,otherwise the system will automatic
start up by method one. The software interface will be showed after the Windows
operating system started up. On the main interface, click all kinds of functions
testing module logo by using the left key of external connected mouse or
tracking ball mouse for doing all tests.
¿ Procedures for Turning Off
Please do not close down the power switch on the faceplate
directly. You should terminate the Windows operating system firstly, and then
press the power supply button when indication for safe turning off appears on
the screen.
Move cursor on the main interface through mouse or press
the ‘QUIT’ key on the faceplate to quit all functional testing units. After
backing to the main interface, press the ‘QUIT’ key again, a dialog window for
confirmation will be ejected on the screen. After your confirmation, you can
turn off the power supply switch on the front panel when ‘You can turn off the
power supply now’ appears on the screen, so the machine can be closed safely.
You can also turn off the device by choosing the ‘start’
menu of the operation system.
Chapter 4 Brief Instruction on Software Operating Method(LY808 Relay Protection Analyzer)
The Relaytestar software is new generational testing
software developed byWuhanhuman Company. Its characteristics are more friendly and beautiful interface,
more complete and powerful functions, and it also preserves its unique
characteristic of simple and concise interface, easy operation and easy to
learn. According to different functions of each testing module, we separate the
testing modules to five groups, general testing, common protection, circuit
protection, components protection and comprehensive function. Each group
includes some sub-menus, such as the ‘common testing’ includes ‘AC Test’, ‘DC
Test’, ‘Harmonic Superposition’, ‘State Series I’ and ‘State Series II’, and it
can be extended at will. On the right of this window, it displays rolling
introduction about the company.
Section 1
Introduction on Common Functions in Menu Bar
Name or symbols of menu items in every testing module are the
same, and its definition and function are almost identiacal. We take the ‘AC Test
module as example for introduction, which can be applied for all functional
modules.
Opening file:The shortcut key is Ctrl+O,
which is used for calling out testing parameters saved in appointed file and showing
the parameters on software interface. If clicking this function, the testing
parameters of current module will be saved as the following default path :E:\
Relaytestar\Para\name of current module\.
● Saving parameters:The shortcut key is Ctrl+S, which is used
for saving the testing parameters on software interface and call out them again
by using ‘Opening parameter’ later. Data will be saved in the default file of
the current module.

Reporting Test:Shortcut key is Ctrl+R, which is used for calling out the test
report saved in appointed file. The contents of test report will be displayed
in the test report window and revising or printing the test report can be
completed in this window. After every test, a dialog box will be ejected by the
system to save the test report. The report will be saved as the following
defaulted path: E:\ Relaytestar\Test Report\name of current module\
● Exit:Shortcut key is Ctrl+X,which is used for exiting current testing module。
● Start Test:It has identical
function as the run key,which is used for
starting the test.
● Stop Test:It has identical
function as the ESC key, which is used for ending the test
normally or compelled terminating program running.
● Short Circuit Calculation:After
clicking it, a ‘short circuit calculation’ dialog box will be opened, which is
used for short circuit calculation and automatically fill the interface with
the calculated results when fault occurs just like the right chart shows. Note
that zero sequence compensating factors must be set correctly when the fault
type is grounding fault.
Section
2 Introduction on Common Button in the
Tool Bar




Attention:
During the operation, if interface data is wrong or you can
not input correctly, you can settle these problems as follows: delete the file
of ‘para’ under 'E: \ Relaytestar \ in Windows system, and then restart the
operating program, all data on the interface will be recovered to the default.
Chapter 5 AC Test
The ‘AC Test’module
is a universal and comprehensive testing module. It has an independent testing
unit with 4-phase voltage and 3-phase current output, also independent testing
units with six phase voltage and six phase current output and an testing unit according
to sequence component output, which can be switched between each other through
3P, 6U, 6I, 12P and five buttons of sequence component. Making use of these
modules, we can carry out AC testing under all conditions in power system (note:
6 phase voltage, 6 phase current, 12 phase voltage-current function are only intended
for Model 1000/1200 ). Their common features are as following: through setting
corresponding voltage or current as variables, giving the variable certain changeable
step size and selecting suitable testing mode (‘manual operation’, ‘semi-automation’
and ‘full-automation’ three modes are available) to test action value, return
value, action time and return time of all kinds of voltage and current
protection conveniently, and calculating return factor automatically. Since the
‘four phase voltage and three-phase current’ unit is used often and the
operating method of other units is basically the same as it, so we only take
the ‘four phase voltage and three-phase current’ as the example to introduce in
detail.
Flexibly controlling output four phase voltage, three-phase
current six phase voltage, six phase current, outputing full twelve phase at
the same time.
Having the function of outputting according to phrase
sequence component.Through setting the value of phrase sequence component directly,
the module combines each phase voltage and current output automatically.
For each phrase voltage and current output, both amplitude
and phase can be set arbitrarily. The amplitude can be set the upper limit.
Every component’s amplitude value, phase and frequency are
variable, and the variable step size can all be set at will.
Ux can be set to be many kinds of output modes combination and
also can be set arbitrary value
Full-automation, self-automation and manually operating are
available,which can be switched between each other in the process of output.
Amplitude, phase, step size and numbers of variable can be
revised directly in the status of output.
Power value can be displayed directly for verifying power
measurer.
Action value, return value, action time and return time can
be measured.
Section 1 Interface Instruction
¢ Set AC Component
After entering the effective value of voltage and current,
click the ‘confirmation (enter)’ key or move the cursor to other place, the
data entered will automatically be saved to three places of decimals. The
default unit of voltage is V, and the default unit of current is A. When
setting the phase, you can enter any angle in the range of -180~360°. If the angle
overflows the above range, the system will switch it automatically into this
range. For example, if entering ‘-181°’, it will be altered to be '179°’
automatically. In the vector diagram window, you can observe the real-time
diagram of each AC vector.
The single phase largest output of AC voltage is 120V. If
you need to output higher voltage, you can connect any two-phase voltage in
series. Their amplitudes may not be the same, but the phases should be reversed
.For example: set Ua to output 120V, 0°, and set Ub to output 120V ,180°, then
the effective output value of Uab will be 240V.
The single phase largest output of AC current can reach 40A
(when six phase current of Model 1000 output at one time, the largest output current
of each phase can achieve 20A, and that of Model 1200 can achieve 30A). If larger current output is
required, you can adopt parallel connection and the phase of each phase should
be the same when operating in parallel. When selecting heavy current output,
thicker and shorter lead wire is prefered, in addition, make sure that output
time is as shorter as possible.
The ‘variable’ column alongside of the effective value set
for AC component is used for choosing whether the output component is
alterable. If you click the ‘variable’ column at the back of certain phase’s
effective value or phase for ‘√’, it means that the
output phase is alterable. Meanwhile, the ‘Step Size’ column will be changed
from gray to highlight, which indicates the ‘Step Size’ setting permissible. The
smallest value of variable step size of amplitude is 0.001, and the smallest
value of variable step size of angle is 0.1.
The column of ‘upper limit’ is used for setting the largest
output effective value of each phase. When doing the test,once the output of certain
phase can’t be estimated and will result
in damage to the relay, you can set an ‘upper limit value’ for this phase,therefore
,the output of this phase will be controlled within the limit value, which
ensure the safe operation of relay.
¢ Ux
Ux is a special phase, it can set many kinds of output
situations:
When setting it to be +3UO、-3UO、+
combining UA and UB with UC output currently to obtain 3UO
component ,and then multiply their coefficient respectively to obtain the UX
output value.The value always varies along with the change of UA, UB and UC.
If Ux is set to equal the value of certain phase such as
UA, the output of Ux is the same as the one of corresponding phase.
If selecting the ‘Any Mode’, the output of Ux is the same
as other three-phase voltage in the range of output and also can vary its
amplitude and angle according to certain step size.
Attention:
There are 6 phases voltage output in the Relaytestar-1000/1200
tester, but there is not an independent
special phase Ux . Consequently, the program assigned the fourth phase voltage Ua
as the special phase Ux.
¢ Parameters Display
The line voltage, zero sequence, positive sequence and
negative sequence components will be shown on the left side of the interface.
Through this window, you can monitor the variable situation of ‘sequence
component’ and ‘line voltage’. The values of this part are calculated
completely according to each phase’s component value given above and can’t be obtained
by setup. Through this window, the operator can observe each sequence component
and values of line voltage when protection is performed, which is convenient
for recording the operation data of protection according to different demands.
For example, when doing low-voltage latching overcurrent test, if the line
voltage is given for protection setting value, you can not only see the value
of phase voltage when protection acts visually, but also can read directly the
value of phase voltage from this window without calculating by operator themselves.
¢ Power Measurer Display Button

When clicking this button, a ‘Power Display’ box will be
ejected just as the right figure shows.
In this displaying box, all kinds of amplitude, phase,
power and other data of secondary side will be displayed default. If the data
of primary side needs to be displayed, for example, when verifying on-the-spot
meter, you only need to select the ‘primary side power and current’ and input
corresponding TV and TA ratio. Click the ‘Power unit is megastage’ for conversion
the power unit from ‘KW、Kvar’ to ‘MW、Mvar’ automatically.
¢ ‘Contact Action’ and ‘Action and Return’
When selecting the ‘Contact Action’ in the column of
testaim, the tester will stop the test automatically when it receives signal of
protective action, and will record the data of relay action at that time.
When selecting the ‘Action and Return’ in the column of
test aim, the tester can test the data of relay action and return, and it can
also calculate the return coefficient automatically.
¢ Modes of Manual Operation, Semi-automatic and Full-automatic
Operation
Mode of Manual Operation
All variables are
controlled by hand. Press the
key or
key on the tool bar, or press the “↓” key or“↑”key on the
keyboard on front panel, each variable will increase or decrease one step. When
relay acts, the tester will give a sound of ‘Di” and record the action value
and time. If needing to test the return value of the relay, decreasing or increasing
the variable till the relay’s contact return, the sound of ‘Di’ will disappear.
The tester will record all necessary return data and calculate the return
coefficient automatically.
Mode of Semi-automatic
Operation
In this mode, all variable will increase or decrease
automatically after starting the test when selecting ‘Increase’ or ‘Decrease’.
You can set the interval of increase or decrease. When the relay acts, the
tester will record action value of selected variables automatically and maintain
output but the variety will be stopped temporarily. Meanwhile, a dialog box
will be ejected for asking the change direction of next step, will you ‘increase’,
‘reduce’ or directly ‘stop’ the test? You should select an order according to
the requirement of test.
Mode of Full-automatic Operation
In this mode, all variables will increase or decrease according
to step size after starting the test when you select ‘Increase’ or ‘Decrease’.
You can set the interval of increase and decrease when protection acts; it will
record necessary data automatically. If the ‘only contact operation’ has been
selected, the tester will stop the test after obtaining the action data automatically;
if the ‘test action value and return value’ has been selected, the tester will
automatically change direction after obtaining the action value and alter the
value in the opposite direction till the contact of tester returns so as to
measure the return value, record it and calculate the return coefficient.
Attention:
1. In the mode of ‘manual Operation’, the speeds of
increase and decrease variable can not be very quickly when it almost achieve
the value of protective operation, so as to ensure the variable stays for
enough times at every step size for producing the action. Only doing like this,
the result measured will be more accurate.
2. During the automatic test, the internal calculator will
be reset to zero with each step process. When measuring the action time of
relay, please select the mode of ‘manual Operation’ and make it to vary slowly
if longer time is needed.
¢ Directly Set Parameter to Alter Output Value in the Output State
During the test, the software permits to use many functions
to directly change output in the state of output:
You can switch the mode of ‘Manual Operation’, ‘Self-automation’
and ‘Full-automation’ in the output state, switch between ‘Increase’ or ‘Decrease’,
or switch between ‘Contact Action’ or ‘Action and Return’. You can change the ‘Time
interval of automatic variety’ in the mode of manual operation.
Whenever parameters need to be amended, it can be changed
among all kinds of modes. Click corresponding ‘Alteration’ box to tick ‘√’ or cancel to complete this operation.
In the mode of ‘Manual Operation’, you can change output of
each phase at one time. The concrete operating procedure is as following:
directly input the amplitude and phase of each phase needing to be amended one
by one (please do not press the ‘confirmation’ key before completing it). After
finishing inputting all values, please press the ‘Confirmation’ key. Then, the tester
will synchronously change output of each phase to be the corresponding input
value .
¢ Input
All input of ‘Relaytestar’ Series Tester share one common
terminal. When connecting the protective action contact, connect one end with
the common terminal of tester and connect another end with any one of input A、B、C、R、a、b、c. Please note
that if the connector has the positive potential,do connect this connector with
common terminal.
In this testing module, input A、B、C、R、a、b、c are effective in default state. The relationship
between them is ‘or’. When certain digital input is not needed, you can select
to close it. When doing the test, switch-off and switch-on contacts of relay
can be connected with any digital input (during the line protection, the
software defaults the digital input R to be the signal incoming end of reclosing.
When connecting the input common terminal (red terminal) with active contact,
we normally connect it with the positive end of power supply. The tester will
record the time in the column of input as soon as the tester receives the trigger
signal of the digital input.
If the trigger signal occurs in multichannels digital input
,the corresponding data wii be recorded.
¢ Confirme the Switch State Change Time
Off/on of contacts of all kinds of relay and microcomputer
protection normally has certain oscillation. To prevent the oscillation from
influencing the test result, we usually set certain ‘Confirme the Switch State
Change Time’. For common relay, ‘Confirme the Switch State Change Time’ is set
to be 20ms,as for the microcomputer type protection, ‘Confirme the Switch State
Change Time’ only needs to be set to be 5ms.
Record Test Result

There
is an area for recording the ‘action value’, ‘return value’ and ‘return
coefficient’ of test result on the lower right of the interface. It can record
three-phase voltage, current, line voltage, voltage, positive sequence,
negative sequence and zero sequence component of current, phase and frequency
of AC, etc. You only need to tick the box before any item. Just as the right
diagram shows
Short Circuit Calculation Button

‘AC
Test’ module is a popular module. When more complex test needs to be simulated,
please click the Short Calculation button in the tool column. A dialog box of ‘Short
Calculation’ will be ejected, in which you can set arbitrarily.
Type of Fault
Four types of fault are available in the pulldown menu:
single phase earthing short circuit, two phase short circuit, three-phase short
circuit or normal state, among which the normal state means that the three
phase voltage is positive sequence rated voltage and three-phase current is 0A.
Fault Direction
It is ‘Forward Direction Fault’ in the default mode. When
reverse fault needs to be simulated for some directivity protection, you can
select the ‘Reverse Fault’ in pulldown menu.
Rated Voltage
It represents the rated phase voltage of the system. The rated
voltage usually is 57.735V.,which refers to the Non-fault phase voltage.
Setting Impedance
According to different setting valued given by the setting
value list, you can set fault impedance according to ‘Z / Ф’ or ‘R / X’ two
kinds of modes on the interface. Selecting which kind of mode to set setting
impedance depends on the setting value list. Whatever you choose,the value of
another kind of mode will be obtained through automatic calculation of the
computer..
Multiple of Short Circuit
Impedance
Above we set the ‘Setting Impedance’ in the setting value
list, but we often verify it in 0.95 times or 1.05 times when doing the test.
So ‘Short Circuit Impedance” = ‘Times Value’ ×’Setting
Impedance’,involving ‘Short Circuit Impedance’ with short circuit calculation
again. When doing the ‘Zero Sequence Protection’ test, the preemptive action of
distance protection can be standed aside through flexible setting of short
circuit impedance and in the case of not exiting the distance protection.
Model for Calculation
When selecting the ‘Maintaining Short Circuit Current’,
certain short circuit current needs to be set. You can calculate the ‘Short
Circuit Voltage’ of corresponding fault type by using the ‘Short Circuit
Impedance’ and this ‘Short Circuit Current’ given. When selecting ‘Maintaining
Short Circuit Voltage’, certain short circuit voltage needs to be set. You can
calculate the ‘Short Circuit Current’ of corresponding fault type by using the ‘Short
Circuit Impedance’ and this ‘Short Circuit Voltage’. When doing the ‘Distance
Protection’ Test, flexible setting the short circuit impedance may avoid the
priority-action of the ‘Distance Protection’ under the condition of not exiting the zero
sequence protection.
Attention:
‘Short Circuit Voltage’ represents the fault line voltage
when two phases is short circuit, while it refers to the fault phase voltage in
the event of other types of short circuits.
Zero Sequence Compensating
Factor
When simulating the ‘Earthing Distance Protection’ Test, the
corresponding zero sequence compensating factor must be considered. Software
gives three setting modes, please set according to the setting mode of zero
sequence compensating factor given in the setting value list.
After finishing the above testing parameters setting,
please click the ‘confirmation’ button, then the software will calculate the
short circuit voltage, current and corresponding angles and fill these data on
the ‘AC Test’ interface at once.
¢ Function of outputting according to sequence component

The
following diagram shows the testing interface of sequence component:
Set directly all kinds of sequence component of
voltage-current needed to be output on the interface. For example, when needing
to output three phase negative sequence voltage,fill the blank after ‘U-’ with this value and software can calculate automatically the amplitude
and phase relations of output voltage of each phase.
Attention:
1. You should note that the amplitude, variation step size
and phase are all sequence components,which are combined by three-phase voltage
or three-phase current but not actual output of single phase of tester. If changing
any sequence component value on the interface (including amplitude and phase) ,software
will real-time calculate corresponding three-phase voltage and current ,which will
be displayed in the listing area on the lower left side of interface. The tester
output voltage and current displayed on the interface rather than sequence
component.
2. U0、I0、U-、I- on the interface are value of each sequence component,equaling to
one third value of 3U0、3I0、3U-、3I- in general use, which is the same as the value displayed in the
result list on the lower left corner of three-phase AC Test interface. When
doing the test, firstly identify which one is the setting values given by
protection, U0、I0、U-、I- or 3U0、3I0、3U-、3I-. If being U0、I0、U-、I-, you can set parameter directly according to the setting value;
if being 3U0、3I0、U-、I-, the actual setting value should divide by 3,and then set
parameters according to new setting value.