System Introduction
The Sweep Frequency Response Analyzer is
used for power transformer with voltage grade of 66kV and above and other
transformers with special purpose. The power transformer is inevitably
vulnerable to impulse of various fault short-circuit current or physical
collision in the process of operation and transportation and the transformer
windings may lose stability under the powerful electro-dynamic force exerted by
such short-circuit current, which could result in permanent deformations such
as local distortion, swell or dislocation and will severely affect safe
operation of the transformer. Deformation of transformer windings is measured
with frequency response analysis method according to national standard
DL/T911-2016/IEC60076-18 for electric power industry, i.e. detect
amplitude-frequency response characteristic of each transformer winding and
make vertical or horizontal comparison of the detection result to judge
possible deformation of the transformer winding based on change of
amplitude-frequency response characteristics.
1、Main Technical Characteristics(LYBRZ-II Transformer winding deformation tester )
Characteristics of transformer windings are
measured with frequency sweep method. Deformations of windings such as
distortion, swell or displacement of 66kV and above transformer are measured by
detecting amplitude-frequency response characteristics of each winding, not
requiring lifting of transformer enclosure or disintegration.
Quick measuring, measuring of a single
winding is within 2 minutes.
High frequency accuracy, higher than
0.001%.
Digital frequency synthesis, with higher
frequency stability.
5000V voltage isolation fully protects
safety of the testing computer.
Able to load 9 curves at the same time and
automatically calculate parameters of each curve and diagnose winding
deformations to provide the reference diagnosis conclusion.
Analysis software has powerful functions
and software and hardware indicators satisfy national standard DL/T911-2016/IEC60076-18.
Software management is humanized with high
degree of intelligence. You only need to click one key to complete all
measurements after setting of parameters.
The software interface is concise and
vivid, with clear menus of analysis, save, report export, print, etc.
2、Main Technical Indicators(LYBRZ-II Transformer winding deformation tester)
Measuring speed: 1 min- 2 min for
single-phase winding
Output voltage: Vpp-25V, adjusting
automatically in test
Output impedance: 50Ω
Input impedance: 1MΩ (the response channel
is built with 50Ω matching resistance)
Frequency sweep scope: 10Hz-2MHz
Frequency accuracy: 0.001%
Frequency sweep manner: linear or
logarithmic, frequency sweep interval and number of sweep points are freely
settable
Curve display:
amplitude-frequency curve
Width
of measuring dynamic range: -100dB~20dB
Supply
voltage: AC100-240V 50/60Hz (use DC12V Adapater recommend)
DIM:
238mm*184mm*40mm
Net
weight: 2.45kg
3、Main Features of Test Analysis Software(LYBRZ-II Transformer winding deformation tester)
Use windows platform compatible with Windows
2000/Windows XP/Windows 7/windows 8/Windows10/Windows11.
Use database to save test data and render
concise and easy data management.
Able to load 9 curves at the same time and
automatically calculate parameters of each curve and diagnose winding
deformations to provide the reference diagnosis conclusion.
Software management function is powerful
that takes into full account of site use demand. Measuring data is automatically
saved and exported to form Word version test report (require installation of
relevant Office software) or JPG photo report to facilitate the user to export
test report.
The software has distinctive humanized
feature. Measuring conditions are mostly options, which exempt the need of many
inputs and bring about easier operation.
The software has high degree of
intelligence. You only need to click one key to complete all measurements after
connection of input and output signals.
The software interface is concise, vivid
and practical.
Part I Operation Flow of System(LYBRZ-II Transformer winding deformation tester)
Ground collector
Connect collector and transformer winding
Connect collector and computer
Start up computer
Power on collector
Log in software
Input information
Select end-frequency and adjust testing
parameter
Select winding
Start testing
Replace test winding
Select winding
Start test
Repeat above process until all winding
tests are done
Analyze data
Export report
Turn off software
Power off collector
Disconnect collector and computer
Remove transformer winding
Test completed.
Part II Preparation
Note: basic operations of computer and
Windows operating system are not contained in the operation instructions.
Please refer to relevant computer books.
Note: basic operations of Windows operating system involved in the
operation instructions are based on Windows 7 operating system. The differences
in operation between other Windows system and Windows 7 system are not
contained in the operation instructions, for which please refer to relevant
computer books.
Part III Test Wiring
3.1 Panel Introduction
Panel of the transformer winding
deformation tester is as shown in Figure 1.
External wiring illustration during Sweep
Frequency Response Analyzer is as shown in Figure 2. Frequency sweep voltage
signal is input from excitation end of the tester to initial end of the tested
transformer winding through input resistance (internal resistance), voltage
signal at the initial end to input end of the tester and voltage signal at the
tail end of the tested transformer winding to response end of the tester.
“Ground” of the Sweep Frequency Response Analyzer as well as enclosure and core
of the “tested transformer” are grounded together.
3.2 Winding Wiring Mode
It is recommended to input frequency sweep
signal of winding deformation frequency response test from tail end of winding
and output from initial end, suspended for non-tested winding. Wiring mode of
winding deformation test varies with different wiring group of the transformer.
YN Wiring
Input impedance of frequency sweep signal
is connected to neutral point O and output impedance to A, B and C
respectively. For the measuring method, interference signal received by
non-measured phase is absorbed by low impedance of the signal generator, as
shown in Figure 3.
Y Wiring
It is required to wire in the following
manner as neutral point has no outgoing wire, as shown in Figure 4.
In this test, input impedance is connected
to A and output impedance to B.
In this test, input impedance is connected
to B and output impedance to C.
In this test, input impedance is connected
to C and output impedance to A.
Interior Connection △ Wiring
Wiring mode of interior connection △ wired
winding is as shown in Figure 5.
In this test, input impedance is connected
to c and output impedance to a,on behalf of a phase.
In this test, input impedance is connected
to a and output impedance to b,on behalf of b phase.
In this test, input impedance is connected
to b and output impedance to c,on behalf of c phase.
Theoretically, the two non-measured
windings that are connected in series first and then connected with the circuit
in parallel in interior connection Δ wiring mode have some effect over the
testing process. However, it is believed that their effect over the non-measured
coil is negligible when attenuation is more than 10dB.
Exterior connection Δ wiring
Wiring mode when windings are disengaged in
measurement is as shown in Figure 6. It is regarded interior connection Δ
wiring if connections are not disengaged, when the wiring mode is as shown in
Figure 7.
In this test, input impedance is connected
to x and output impedance to a,on behalf of a phase.
In this test, input impedance is connected
to y and output impedance to b,on behalf of b phase.
In this test, input impedance is connected
to z and output impedance to c,on behalf of c phase.
Transformer with Balance Winding
The transformer with balance winding must
be ungrounded in test, as shown in Figure 7.
Part IV System Test
4.1 Start of “SFRA test” Program
1)Double click the icon
of “SFRA
test” to start the program of “transformer winding deformation test system”.
2)Enter the main program interface titled “Sweep
Frequency Response Analyzer” after the start process (double click the small
icon
at the
top left corner of the screen to switch to the desktop. Please do not click the
icon in the process of test.)
The software main interface consists of 7 parts:
(A)Test Curve Display Area
The area displays test curve with frequency as X-coordinate and dB
value with Y-coordinate (amplitude-frequency test) or angle value
(phase-frequency test). The label below consists of:
Curve type label: to mark the current display is
“amplitude-frequency curve” or “phase-frequency curve”. Click the label to
switch between the two types (require hardware support).
Sweep mode label: to display the current sweeping mode is linear
sweeping or logarithmic sweeping. Click the label to switch between the two
modes.
Start frequency label: to display start frequency of current
sweeping. Click the label to switch among different start frequencies.
Stop frequency label: to display stop frequency of current sweeping.
Sweeping point number label: to display total point number of
current sweeping. Click the label to switch among different point numbers.
(B)Status Display Area
The status display area displays working status of the current
equipment.
(C)Operating Zone
There are two keys in the operating area,
start
and
stop
that display in turn according to service
status, i.e. “start” displays under stop status and “stop” under start status.
(D)Test Parameter Setting Area
Area D displays parameter setting window
that is used for setting of test parameters, including winding wiring method,
category , Tap position and number of the winding to be tested, sweep stop frequency,
etc.
(E)Curve Description Area
Area E displays description information of
the current curve. The label in a color contains description information of its
corresponding curve in the same color.
(F)Data Selection Area
What locates at the top right corner (F) is
data selection area. Test data applies hierarchical management, where the first
grade is name of substation, the second grade name of transformer, the third
grade category and number of transformer winding and the last grade existing
data. Data name is displayed in the manner of “data type @ test time”. Data
displayed in the part matches with content of the label in area (A). When
“amplitude-frequency curve” is displayed, the data selection area displays test
result of the amplitude-frequency curve and when “phase-frequency curve” is
displayed, the data selection area displays test result of the phase-frequency
curve.
When “amplitude-frequency curve” or
“phase-frequency curve” is displayed, the test result is displayed in area A
when relevant data is clicked.
(G)Function Key Area
Keys in the function key area (G) will
switch automatically and display dynamically based on the use function.
4.2 Frequency
Response Method Test
Environment and Wiring Confirmation
The system is wired according to
requirements of 3.2 winding wiring mode.
Tap position of the transformer is adjusted
to the maximum impedance position (the first tap)
The surrounding environment is free from
strong electromagnetic interference.
Software Log-in
Double click the icon
of
“Sweep Frequency Response Analyzer” on the desktop. The system will flash
through the welcome interface and then enter the test interface. The system
will have following dialogue box if equipment is not connected:
Occurrence of the above dialogue box is
generally caused by connection failure of equipment. In this case, first check
whether equipment is connected to USB interface of the computer and then check
whether equipment power supply is switched on.
Information Input
Transformer information log-in interface
(as shown in the figure below) is entered when equipment is connected, where
you may input or select information in relevant textbox and click save key so
that the system will enter the test interface.
Please input carefully according to the
transformer nameplate while inputting information as all information is
automatically saved together with the test result and incorrect input may
affect the contents of the report.
Sweeping Mode Confirmation and Modification
1、 Selection of Sweeping Mode
Click “Stop Frequency”
to select test stop frequency and then the
system will automatically set parameters to the set parameters according to the
set sweeping parameters, including start frequency, sweeping mode, and sweeping
point number. To adjust, click the parameter label in area A to switch automatically
(the label automatically turns green when the mouse pointer moves to a
changeable label).
2、Change of Default Information
To readjust the default setting
information, click “Stop Frequency”
key
with right mouse button to let the function menu pop up. The information
setting window (as shown in the figure below) will pop up when “setting” is
selected, where you may adjust the default sweeping information and restart the
software after adjustment. Then the system will test with the adjusted default
information.
The above adjustment is used for setting of
default information that is distinguished by the value of “stop frequency”.
Actually, adjustment is generally performed as required during the first time
use in practical application and is not performed later unless there is
regulation or special requirement.
3、Change of Sweeping Parameters
Change of sweeping parameters is used for
testing of complicated parameter combinations. The system doesn’t have memory
function and will recover automatically once quit.
Click parameter label in the curve display
area (A) before sweeping to change information other than stop frequency in the
manner of cyclic adjustment.
Change of sweeping parameters is applicable
to single test with measuring result requirement or for the sake of research,
generally not requiring adjustment.
Test
You may start data measurement with
frequency response method after setting of basic test information. The system
will automatically complete frequency sweep after “START” key is clicked. The
key will turn to
key in the process of test that could stop
the current sweeping once clicked. The test pauses once the signal curve
display area is clicked and proceeds when clicked again.
After completion of a test item, change the
wiring mode, change software setting information, click again
key,
measure the next item and repeat the above operations until all measurement
items are completed.
The test waveform display area is unfolded
when the test curve display area (A) is double clicked in the test process,
which contains waveform display, input voltage peak value (red), response
voltage peak value (yellow), amplification factor and X-coordinate time information
used for signal research.
4.3 Correlation Analysis
Curves in area E are automatically divided
into three groups, 1-3 as a group, 4-6 as a group and 7-9 as a group and
correlation analysis of each group of curves is performed inside the respective
group. Once
is
clicked, report display window will pop up at the left side that displays
contents of the current test report. The operator may reconfirm and re-input
information and click
on the
report display window to let the save dialogue box pop up, where the operator
may set file name, file type and save path. The result is saved in “FRA_data”
of disk D by default with file name of “print report” + “print time”.
4.4 Data Echo
The system is able to echo saved data. By
selecting name of power station, name of transformer, test category and time,
as well as winding type and time in turn in area F, the completed test result
is called out. By default, the data is displayed at the position of the first
curve and displayed downwards with progressive increase of the selection
result. When the number of curves comes to the maximum (9 curves), the curve no
longer increases and you may select the curve to be replaced for progressive
replacement in this case. When a curve is decided not requiring analysis, you
may right click “clear curve” on the curve description information (E) so that
the curve will be removed out of the analysis list automatically.
Curves in area E are automatically divided
into three groups, 1-3 as a group, 4-6 as a group and 7-9 as a group and
correlation analysis of each group of curves is performed inside the respective
group. Therefore, it is required to ensure the curves to be analyzed are within
the same group, or otherwise you cannot get correct analysis result.
When “analysis”
is clicked after selection of curve, the
report display window will pop up at the left side. All other operations are
the same as operations described in 4.3.
4.5 Report Saving Position
Report is saved under folder of disk D with
the folder hierarchy of:
D: \FRA_data\test report+ print time. doc
or test report+ print time. jpg.
The report could be WORD document or JPG
photo, subject to the option selected in saving.
Part V Tester Maintenance
The section provides basic maintenance data. Please do not try to
disintegrate, modify and repair the Sweep Frequency Response Analyzer.
5.1 Basic Maintenance
Regularly scrub surfaces of the tester and
its accessories with a clean cloth.
Put the tester at a clean place with low
humidity and protect it against entry of dirt and dust. Put the tester into its
packing case when not used and keep the packing case level.
5.2 Senior Maintenance
To be proceeded by professional technicians
of the Company.
Part VI Ordering and Service
6.1 Damages of the tester as a result of product quality issue within 18
months since its delivery will be repaired free of charge; for damages due to
other reasons, the Company only charges repair cost.
6.2 We provide lifetime maintenance and technical services for the
products.
6.3 Please contact us immediately upon discovery of any abnormality in
the tester. We will provide the most convenient solution for you. DO NOT disassemble the tester!